Description:
You asked unit 1 for two registers at 3000 (01 03 0B B8 00 02) and got back 01 83 02. An exception response sets the top bit of the function code: 0x03 + 0x80 = 0x83, "function 03 failed". The next byte is the exception code (Modbus Application Protocol V1.1b3 §7):
01 Illegal Function
02 Illegal Data Address
03 Illegal Data Value
04 Server Device Failure
0A Gateway Path Unavailable
0B Gateway Target Device Failed to Respond
0A and 0B come from a gateway, not from the device behind it.
Fix: 02 → check the address offset (40001 is register 0). 03 → check the count (1 to 125 registers per read). 01 → the device doesn't support that function.
Modbus Poll for Mac decodes every frame and names the exception: https://voltrus.id/modbus-poll/?utm_source=youtube&utm_medium=social&utm_campaign=reach-03
Modbus addressing explained: https://voltrus.id/modbus-poll/blog/modbus-addressing-explained/?utm_source=youtube&utm_medium=social&utm_campaign=reach-03